Takex TAK-FS3000 Flame Sensor

UV Ceiling Mount with Speaker

Description

Features

  • External Open Collector Output for connection with other systems
  • Alarm message played through In-Built Speaker – adjustable up to 80dB
  • Variable response timer – 0.2 Sec, 1 Sec, 6 Sec, 30 Sec
  • 10 Metre detection area
  • Powered by 2 x Alkaline type 3 3V Batteries (included)
  • Optional Lithium Battery
  • Max 300mA (Alarm at Max Volume)
  • Battery Life – approx 2 years using Alkaline batteries
  • -10 to 60C Ambient Temperature

Specifications

Detection system

Ultraviolet rays detection
(detected wave length 180~260nm)

Detection distance

10m (33ft) max. (7cm flame)

Detection angle

Approx. 120 degrees (conically)

Detection timer

0.2secs, 1sec, 6secs, 30secs.

Power supply

Type-3 alkaline battery (LR6) x2 (3V) – included
Lithium battery (CR17450E-R-2-CM2) x1 (3V) – optional

Power consumption

Standby: 70μA or less
Alarm: 300mA or less (at max. volume)

Battery life

Type-3 alkaline battery: approx. 2 years (at standby)
Lithium battery: approx. 5 years (at standby)

LED (red)

LED alarm: blinking during message output
Low battery: light on 0.1 sec every 5 sec.

Message output

Operation: output warning message when detecting flames
Message selection: 4 options (English, Spanish, French, Italian)
Volume: mute – 80dB or more at 1m (3.3ft) ahead

External output

NPN open collector output
30V (DC) 50mA, one-shot operation (ON when outputting)
Output time: same as message output time

Wiring

Terminals

Ambient temperature

-10°C to +60°C (+14°F to +140°F)
(battery performance may decrease below 0°C and above 40°C

Installation

Indoor (ceiling or wall mount)

Weight

Approx. 230g (8.1oz)

Appearance

ABS resin (white)

Supplied accessories

· Battery case (Type-3): 1pc
· Type-3 alkaline battery (LR6): 2pcs
· Sensor locking screw: 1pc
· Tapping screw: 2pcs

 

Blog Navigation